Hagan Power Positioner 4 x 5 Torque Type Floor Mounted


File Size = 2030 KB
File Size = 2623 KB
FEATURES
  • True Positioning Devices – All power positioners assume a definite position of the crosshead or operating lever for each demand signal variation through the action of an integral feedback mechanism.
  • Mounting Variety - Models are available for convenient wall, swivel, or floor mounting. These positioners are often mounted directly on lever type valves by the valve manufacturer.
  • Characterized Positioner – All positioners are equipped with a standard rotary cam or cam bar which produces a straight line relationship between input signal and output motion. Square or square root and blank cams are available.
  • Air Lock – Designated models are equipped with an internal locking mechanism which stops and locks the positioner in the control position existing at the moment of air supply failure until air pressure is restored. System air locking schemes are also available.
  • Fail Safe – Designated models can be equipped to drive the positioner to full open or full closed in case of air supply failure. NOTE: This feature should not be used with the air lock feature.
  • Manual Operators – All torque type positioners are equipped with either a manual operating lever or a manual operating handwheel.
  • Ambient Temperature – Positioners are generally suitable for operation from 0 to 140°F (-17,8 to 60°C) with a maximum rating of 300°F (149°C) for certain high temperature models.
  • Dust Cover and Internal Heater – A dust cover is provided with or without heater and thermostat for certain torque type models.
  • Limit Switches and Position Transmitters – Limit switches and position transmitters are available on designated models.
  • Power Air Supply – Clean dry instrument air at 45 to 120 psig is required for cylinders of 8 inch diameter or less. For cylinders over 8 inches in diameter, the maximum air pressure for standard service is 100 psig and 250 psig for heavy duty service.
Torque & Load Data
Stall Torque400 ft.-lbs. (542 N.m) with 100 psig (689 kPa) air supply
Maximum Friction Load50% of control torque
Maximum Allowable Weight Load140 ft.-lbs. (189 N.m)

Options

Heater and thermostat
Air lock and positive mechanical lock
Manual lock
Limit switches – standard or heavy duty
Minimum stop
Fail safe
I/P signal convertor

Accessories
Filter regulator is included
Clevis and pin are included

DESCRIPTION

Industry needs muscle to control process valves, dampers and feed mechanisms accurately and in response to a demand signal. Emerson’s Rosemount Analytical pneumatic power positioners have been satisfying these exacting control requirements for many years in countless applications – from steel mills to refineries – where positioning speed and accuracy are taken for granted.

Rosemount Analytical power positioners are manufactured in cylinder sizes from 2½ to 8 inches in diameter with strokes of 5 to 14 inches. They come in thrust and torque models for wall, swivel or floor mounting and with accessories such as limit switches, position transmitters, heated enclosures, air failure lock and characterized cams that provide an output motion that is a function of the input signal.

The Rosemount Analytical 4 x 5 Torque Type Power Positioner accepts standard pneumatic signal ranges and produces a 0 to 80° proportional shaft rotation. The options available include analog position transmission and/or contact closure for remote use, and position lock up on power air supply failure.

BENEFITS
  • Accuracy
  • Reliability
  • Simple maintenance because of rugged frame construction
  • Efficient torque and power at a minimum cost
  • Fast response to small input signal changes due to high internal gain