Key
Specifications |
| Measurement Principle |
Pulsed, free propagating radar 5401: ~6 GHz 5402: ~26 GHz |
| Measuring Range |
98 ft (30 m) from flange |
| Instrument Accuracy |
5401: ±0.4 in (±10 mm) 5402: ±0.1 in (±3 mm) |
| Repeatability |
±0.04 in (±1 mm) |
| Output |
4-20mA with superimposed digital HART® communication FOUNDATION® Fieldbus |
| Temperature/Pressure Rating |
Refer to the Product Data Sheet (PDF@1500kb) |
| Ex-Approvals |
Intrinsic safety or Explosion / Flame-proof (ATEX, CSA, IECEx, FM, ...) |
| Display |
5-digit integral display (Optional) |
| Output Variables |
Level, Distance, Volume, Level Rate, Signal Strength,
Housing Internal Temperature, Aout current and % of Range |
| Enclosure |
Polyurethane-covered die-cast Aluminum housing with dual
compartments. |
| Ingress Protection |
Type 4X, IP66, IP67 |
| Fieldbus Functionality |
Link-master device (backup LAS), Block Instantiation, PlantWeb Alerts, Methods |
| Fieldbus Blocks |
Resource
3xTransducer
6xAnalog Input (30 ms)
PID (40 ms)
Arithmetic, Input Selector, Output selector (65 ms)
Signal Characterizer (75 ms)
|
| Configuration Tools |
Radar Master, AMS, DeltaV, 275/375, or any other DD- or EDDL-compatible host. |