Hytork®'s 'CATS' Solenoid Valve |
|
|
| |
Download
'CATS' PDF Brochure
'CATS'
Direct Mount (NAMUR) Directional Control Valves
Valve
Automation Center
Hytork®'s 'CATS' (Clean
Air
To
Springs)
is a solenoid valve designed specifically
for superior operation of pneumatic actuators. All spring return
actuators that use a 3-way solenoid valve require air to enter and leave
the spring chambers. As compressed air is introduced to the actuator to
push the pistons apart, air from the spring chambers must be allowed to
vent. During the fail or spring stroke, the compressed air between the
pistons must exhaust to permit the springs to drive the pistons
together. This piston movement creates a vacuum in the spring chambers
which is usually filled by ambient air that may contain dirt, abrasives,
corrosives and moisture of which are bad for the actuator - reducing its
performance and life.
A wrong solution for this problem is the use of a 4 way solenoid valve
(sometimes referred to as "air assist"). It does prevent the ambient air
from entering the actuator, but it will also pressurise the spring
chambers. The actuator now acts like an air to open, air to close unit.
In the unlikely event of a spring breakage or if the valve torque
increases, due to line media build up within the valve, the actuator
would still appear to operate normally until its fail action was needed
in an emergency. At this most critical time, with supply air not
available, the actuator could not perform as intended and it's function
as a safety device would be defeated.
Hytork's CATS solenoid valve prevents
this undesirable action from happening.
As the solenoid is de-energised, permitting the
springs to push the pistons together, an internal by-pass in the CATS
valve permits some of the exhausting air to fill the spring chambers at
atmospheric pressure while the remainder exhausts to atmosphere. No
ambient air enters the actuator.
|
 |
Only clean supply air
gets into the actuator - Air that was
normally planned to be vented!- There is
no pressure build up that can lead to false torque availability on the
fail stroke, as in the case of air assisted springs!
No extra clean compressed air is used!
The HYTORK® CATS solenoid valves can be supplied in all popular voltages
and electrical classifications and with optional manual override and
speed controls.
The HYTORK® CATS can also be used on Double Acting
actuators as well as spring return actuators with a simple gasket
rotation. This means it is only necessary to hold inventories of one
style of solenoid valve: a further cost saving.
HYTORK® CATS solenoid:
- inexpensive insurance for maximum reliability
and actuator life.
- the easiest to install and the most rugged.
- NAMUR, not a single source special.
|
| |
Back To
Top |
|
Why CATS?
|
| |
Maximises actuator life.
Reduces installation and initial costs.
Prevents actuator seal failure.
Prevents corrosives from entering actuator.
Prevents dirty air from entering actuator.
Proves that the actuator springs are working
correctly every stroke.
NAMUR
standard - Easiest assembly possible -
only two mounting screws.
Eliminates brackets and tubing - mounts directly
to the NAMUR pad on the actuator.
Only one style of solenoid valve required for
Spring Return and Double Acting actuators - reducing inventory costs.
Further reduced installation costs when used with
the
COSTSAVER
Backwire system.
|
| |
Metric
Specifications |
| |
Materials of construction:
- Valve body aluminium:
- (Brass and 303 Stainless Steel available)
Operating pressure & temperature:
- 2 - 8 bar (30 - 120 psi)
- Maximum ambient temperature 80ºC (172ºF)
Cv value:
Coil connections available:
- M20, PG9, Plug & Socket, 1/2" NPT
Coil options:
- Weather Proof:
- to IP65,
- AC Voltages: 6, 12, 24, 50, 110, 200, 240,
440 (50 & 60Hz)
- DC Voltages: 6, 12, 24, 48, 110, 250
- Explosion Proof:
-
Certified
to NEMA, CSA, FM, CENELEC & SAA requirements
- AC Voltages (EExd IIC T4): 50, 110, 120, 200,
240, 80/440 (50 & 60Hz)
- DC Voltages (EExd IIC T6): 12, 24, 110, 240
- Intrinsically Safe:
- Approved as a low energy device for use in
all hazardous environments. This coil operates within the constrains
of the power restriction imposed by the use of safety barriers and
similar devices. Intrinsically safe electrical equipment is the only
accepted form of protection for high risk areas where an explosive
mixture occurs more or less continuously.
- Certified to:
- CENELEC
- FM
- CSA
- SAA
- For use in Zone 0 locations Group IIA, B & C
(EExia IIC T6) :0.4 Watt, 24 VDC Coil.
- Low Power:
- Type N:
- Certified for use in Zone 2 areas only
- AC Voltages (Exd IIC T4): 50, 110, 120, 200,
240, 80/440 (50 & 60Hz)
- DC Voltages (EExd IIC T6): 12, 24, 110, 240
Options:
- Manual overrides
- Speed controls
- Manual reset
- Dual coil valves
- True "fail in last position" Single coils
|
| |
Back To
Top |
|
Imperial Specifications |
| |
Materials of construction:
- Valve body aluminium:
- (Brass 303 Stainless Steel and composite
available)
Operating pressure & temperature:
- (30 - 150 psi)
- Minimum ambient temperature -40ºF
- Maximum ambient temperature 150ºF (167ºF
available)
Cv value:
- 1.2 - 1.4 (0.55 available)
Coil connections available:
- DIN on NEMA 4
- 1/2" NPT conduit hub with 18" leads on NEMA 4,
7, 9
- Other connections available, consult factory
Coil options:
- Weather Proof:
- NEMA 4
- AC Voltages: 12,120, 240 480 (50 & 60Hz)
- DC Voltages: 12, 24, 48 & 125
- Explosion Proof:
- NEMA 4, 7 & 9
-
Certified
to UL, CSA.
- AC Voltages 24, 120, 240 & 480 (50 & 60Hz)
- DC Voltages 12, 24, 48 & 125
- Intrinsically Safe:
- Approved as a low energy device for use in
all hazardous environments. This coil operates within the constrains
of the power restriction imposed by the use of safety barriers and
similar devices. Intrinsically safe electrical equipment is the only
accepted form of protection for high risk areas where an explosive
mixture occurs more or less continuously.
- Certified to:
- CENELEC EEx e m
- FMRC and CSA approvals are available:
- Low Power:
- 0.6 & 0.7 Watt, 24 VDC Coil.
Options:
- Manual overrides
- Speed controls
- Manual reset
- Dual coil valves
- True "fail in last position" Single coils
|
|
|
| |