Emerson Process Management Website Home Emerson Corporate BusinessEmerson Corporate website Company OverviewEmerson Corporate BrandsEmerson Corporate Investor Relations  
Search Emerson Process Management WebsiteEmerson Process Management PlantWebEmerson Process Management Industry CentersEmerson Process Management News & EventsEmerson Process Management ContactsEmerson Process Management Global Presence


 
 

 

Valve Actuator Matrix

Tabulated below is a valve actuator product matrix to provide you with an overview of the major features available for these product lines. Once you have determined the product you believe suitable for your application, you can click on the product name to access more detailed information.
 

  Valve
Operation
Required
Services
Fail Action Torque/Thrust
Mechanism
Torque Range
lbs.in (Nm)
Thrust Range
lbs (N)
TorqPlus R E DA or SR EM 100 - 10,000
(11-1,130)
N/A
RPC-Series R P DA or SR R&P 125 - 16,500
(14 - 1,864)
N/A
CBA-Series R P DA or SR SY 697 - 11,560
(78 - 1,306)
N/A
HD/T-Series R P or H  DA or SR SY 2,727 - 422,886
(308 - 47,783)
N/A
G-Series R P or H DA or SR SY 12,465 - 6,139,796
(1,408 - 693,762)
N/A
WellGuard L-API P SR D N/A 5,000 - 35,475
(1,124 - 7,975)
Gas/Hydraulic R or L HPG or N2 DA SY or PN 2,295 - 6,000,000
(259 - 677,966)
2,898 - 640,800
(651 - 144,051)
PressureGuard R or L None SR SY or PN 2,000 - 100,000
(226 - 11,300)
500 - 25,000
(112 - 5,620)
GVO-Series L P or H DA or SR PN N/A 386 - 500,000
(86 - 112,400) 
 
Matrix Key:
 
  • Valve Operation
    This indicates the type of valves that can be automated by the valve actuator, where:

    R = Rotary Quarter-Turn (90°) Valves
    L = Linear Rising Stem Type Valves
    L-API = Linear API Valves
  • Required Services
    This indicates the type of supply that the actuators require, where:

    E = Electrical
    P = Pneumatic
    H = Hydraulic
    HPG = High Pressure Pneumatic or Natural Gas
    N2 = Nitrogen (all pneumatic actuators are suitable for use with nitrogen)
    None = No external supplies are required
  • Fail Action
    This indicates whether the actuator is double-acting (requires supply pressure to open and close the valve) or spring-return (requires supply pressure to either open or close the valve and uses a spring to return), where:

    DA = Double-Acting
    SR = Spring-Return 
  • Torque/Thrust Mechanism
    This indicates the primary mechanism used to generate the output torque or thrust of the actuator, where:

    EM = Electric Motor
    R&P = Rack & Pinion
    SY = Scotch Yoke
    D = Diaphragm
    PN = Piston
  • Torque Range
    This is an approximate guide to the torque output range of the actuator series.
  • Thrust Range
    This is an approximate guide to the thrust output range of the actuator series.

Back to Top


Send comments to:
WebMaster.ValveAutomation@EmersonProcess.com


Last Updated 11/14/08


© Emerson, 1996-2008