Hytork® AFS-800 Actuator Air Consumption Figures
 

 

 


Hytork® AFS-800 Actuator Air consumption Figures - Imperial
Hytork® AFS-800 Actuator Air consumption Figures - Metric

 
Imperial
 

 
Combined free air volume of both air Chambers in3 Free air
required to charge chambers at
30 psi (in
3)
Free air required to charge chambers at
40 psi (in
3)
Free air required to charge chambers at
50 psi (in
3)
Free air required to charge chambers at
60 psi (in
3)
Free air required to charge chambers at
70 psi (in
3)
Free air
required to charge chambers at
80 psi (in
3)
Free air
required to charge chambers at
90 psi (in
3)
Free air
required to charge chambers at
100 psi (in
3)
3433.93 10439.16 12774.27 15109.31 17444.38 19436.07 22114.53 24449.61 26784.69
 
Combined free air volume of centre chamber and swept volume in3 Free air required to fully open the Actuator at 30 psi (in3) Free air required to fully open the Actuator at 40 psi (in3) Free air required to fully open the Actuator at 50 psi (in3) Free air
required to fully open the Actuator at
60 psi (in
3)
Free air
required to fully open the Actuator at 70 psi (in
3)
Free air required to fully open the Actuator at
80 psi (in
3)
Free air required to fully open the Actuator at
90 psi (in
3)
Free air required to fully open the Actuator at
100 psi (in
3)
845.54 2570.45 3145.42 3720.39 4295.36 4785.78 5445.3 6020.27 6595.24
 
Combined free air volume of Endcap and swept volume
in
3
Free air required to fully close the Actuator at
30 psi (in
3)
Free air required to fully close the Actuator at
40 psi (in
3)
Free air required to fully close the Actuator at
50 psi (in
3)
Free air
required to fully close the Actuator at
60 psi (in
3)
Free air
required to fully close the Actuator at
70 psi (in
3)
Free air required to fully close the Actuator at
80 psi (in
3)
Free air required to fully close the Actuator at
90 psi (in
3)
Free air required to fully close the Actuator at
100 psi (in
3)
801.94 2437.90 2983.22 3528.54 4073.86 4538.98 5164.49 5709.81 6255.13

NOTE:

Once the reserve air chambers have been fully charged to their pre-set working pressure, there will be no change in chamber pressures even as the unit is being modulated, unless there is an interruption to the air supply.
If the air supply is broken or disconnected the internal versa valve contained within the control chamber will switch and close down the Actuator.
The chamber pressure will be reduced by approximately 25%, after failure the Actuator will remain inoperative until the air supply is restored.

If an electrical failure occurs, the Solenoid valve coil will de-energise allowing the Solenoid spool valve to move to the rest position and the Actuator will close.
During and after electrical failure the air chambers will remain at full working pressure, the Actuator will remain inoperative until the power supply is restored.
 

 

Back To Top

 

Metric

   
Combined free air volume of both air Chambers (cm3) Free air required to charge chambers at
3 Bar (cm
3)
Free air required to charge chambers at
4 Bar (cm
3)
Free air required to charge chambers at
5 Bar (cm
3)
Free air required to charge chambers at
5.5 Bar (cm
3)
Free air required to charge chambers at
6 Bar (cm
3)
Free air required to charge chambers at
6.5 Bar (cm
3)
Free air required to charge chambers at
7 Bar (cm
3)
56294 225176 281470 337764 365911 394058 422205 450352
.  
Combined free air volume of centre chamber and swept volume (cm3) Free air required to fully open the Actuator at
3 Bar (cm
3)
Free air required to fully open the Actuator at
4 Bar (cm
3)
Free air required to fully open the Actuator at
5 Bar (cm
3)
Free air required to fully open the Actuator at
5.5 Bar (cm
3)
Free air required to fully open the Actuator at
6 Bar (cm
3)
Free air required to fully open the Actuator at
6.5 Bar (cm
3)
Free air required to fully open the Actuator at
7 Bar (cm
3)
13861 55446 69307 83168 90099 97030 103960 110891
.  
Combined free air volume of Endcap and swept volume (cm3) Free air required to fully close the Actuator at
3 Bar (cm
3)
Free air required to fully close the Actuator at
4 Bar (cm
3)
Free air required to fully close the Actuator at
5 Bar (cm
3)
Free air required to fully close the Actuator at
5.5 Bar (cm
3)
Free air required to fully close the Actuator at
6 Bar (cm
3)
Free air required to fully close the Actuator at
6.5 Bar (cm
3)
Free air required to fully close the Actuator at 7 Bar (cm3)
13147 52586 65733 78879 85453 92026 98599 105172

NOTE:

Once the reserve air chambers have been fully charged to their pre-set working pressure, there will be no change in chamber pressures even as the unit is being modulated, unless there is an interruption to the air supply.
If the air supply is broken or disconnected the internal versa valve contained within the control chamber will switch and close down the Actuator.
The chamber pressure will be reduced by approximately 25%, after failure, the Actuator will remain inoperative until the air supply is restored.

If an electrical failure occurs, the Solenoid valve coil will de-energise allowing the Solenoid spool valve to move to the rest position and the Actuator will close.
During and after electrical failure the air chambers will remain at full working pressure, the Actuator will remain inoperative until the power supply is restored.

 